Model NO.: GDGY
High Voltage Output: 1000~2000V
Frequency: 50Hz/60Hz
Size: 450mm*360mm*310mm
Instrument Weight: <18kg
Trademark: Gold
Transport Package: Wooden Case
Specification: ISO
Origin: Chongqing of China
HS Code: 9031809090
GDGY Insulating Oil Tan Delta Tester Oil Cup Test-Bridge for Dielectric LossI. Introduction
GDGY Insulating Oil Tan Delta Tester is dedicated to insulating oil liquid medium of dielectric loss angle and volume resistivity testing of high precision instruments.
II. Features
1 Â Light weight, small size, test safe operation, a complex dual-use, portable integrated structure.
2 Â With all-digital technology, the operation is intelligent and automatic;
3 Â With a large screen (240 * 180) LCD display;
4 Â Test results can be printed out;
5 Â Easy operation, the operators without professional training can be skilled use.
6 Â One heating part adopts the most advanced of the current high-frequency induction heating method, the heating oil-cup with non-contact with the heater, heating evenly, fast and convenient control and so on.
7 Â AC Test Power Supply with AC-DC-AC conversion means, effectively prevent the mains voltage and frequency fluctuations of the dielectric loss test the accuracy of the impact of even the generator, the instrument can also be run correctly.
8 Â Internal standard capacitors SF6 inflatable 3-pole capacitor, the capacitor dielectric loss and electrical capacity is not the ambient temperature, humidity, etc., to guarantee precision equipment in line even after prolonged use.
III. Internal Integration
1 Â Dielectric loss oil cup;
2 Â temperature controller;
3 Â temperature sensor;
4 Â dielectric loss test bridge;
5 Â AC high voltage test power supply;
6 Â standard capacitors;
7 Â high impedance meter
8 Â DC high voltage test power supply and other major components.
IV. Main Technical Specs
Â
1 | Condition of Use | -5ºC_40ºC        RH<80% | ||
2 | Power Source | AC 220V±10%     Without Frequency Limit | ||
3 | High Voltage Output | 1000V_2200VÂ Â Â Â Â Every 200V | ||
 | Precision | 2% | ||
 | Capacity | 50VA              Output Current 25mA | ||
4 | Temperature Control Induction Stove | Maximal Power  500W | ||
5 | TemperatureControl Range | <100ºC | ||
6 | Temperature Measuring Error | ±0.5ºC | ||
7 | Control Temperature Error | ±1ºC | ||
8 | Control Temperature Time | Room Temperature 90ºC         <20min | ||
9 | Measuring Range | tgδ        Without Limit | ||
 |  | Cx        15PF-300PF | ||
 |  | Rx         10M-10T | ||
10 | Precision | Δtgδ: ΔCx : ΔRx : |
±(Reading*1.0%+0.020%) ±(Reading*1.0%+0.5PF) ±Reading * 10% |
|
11 | Relative Dielectric Loss Constant | εr   | Calculated Automatically | |
12 | Volume Resistivity | ÏÂ Â Â Â | Calculated Automatically | |
13 | Dimension | 450(L)×310(W)×360(H) | ||
14 | Weight | 18Kg |
Â
Liquid Barium Zinc Stabilizer,Leather Stabilizer,Ba Zn Stabilizer,Barium Zinc Liquid Stabilizer
Jiangsu Greya New Material Technology Co., Ltd. , https://www.greyastabilizer.com